How to use or fill out duct air leakage test report with our platform

Form edit decoration
9.5
Ease of Setup
DocHub User Ratings on G2
9.0
Ease of Use
DocHub User Ratings on G2
  1. Click ‘Get Form’ to open the duct air leakage test report in the editor.
  2. Begin by filling in the 'ENGINEER', 'PROJECT', 'BLDG. NO.', and 'LOCATION' fields at the top of the form. Ensure that all information is accurate for proper documentation.
  3. Enter the 'DATE' in M/D/YYYY format to record when the test was conducted.
  4. In the 'LEAKAGE TESTS' section, review any notes regarding testing requirements based on duct pressure class ratings. This will guide you on whether testing is necessary.
  5. Proceed to fill out the 'TEST RESULTS' section, including details about the test apparatus used, such as blower specifications and orifice sizes.
  6. Complete the final sections by entering measured leakage values and obtaining signatures from witnesses to validate the results.

Start using our platform today for free to streamline your document editing and ensure accurate completion of your duct air leakage test report!

be ready to get more

Complete this form in 5 minutes or less

Get form

Got questions?

We have answers to the most popular questions from our customers. If you can't find an answer to your question, please contact us.
Contact us
Verification can take place via either a post-construction test or a rough-in test. For the post-construction test, leakage measurement must be made across the entire system, including the manufacturers air handler enclosure, with all register boots taped or sealed at a test pressure of 0.1 inches w.g. (25 Pa).
Test Procedure: The system (ductwork or piping) is pressurised to a specified level using a fan or a blower. The rate of air loss is measured, usually by how much airflow is needed to maintain the test pressure. The leakage rate is compared to standard allowable limits (e.g., per DW/144 for ductwork).
Standard: The measured duct leakage must not exceed 0.06 CFM25 x floor area (in square feet) served by the system. Duct testing device. Manometer (a second manometer is helpful, but not required) Tape and paper or duct mask to seal registers.
Based on the protocol for Total Leakage Testing, or Leakage Testing to Outdoors duct leakage in new construction shall not exceed 0.06 CFM25 x floor area (in square feet) served by the system for leakage to outdoors or 0.08 CFM25 x floor area (in square feet) served by the system for total leakage.
ASHRAE Standard 90.13 (section 6.4. 4.2. 2) requires air leakage testing of 100% of all outside ductwork and 25% of representative sections of all other ductwork designed to operate at a static pressure in excess of 3- inch water gauge.
be ready to get more

Complete this form in 5 minutes or less

Get form

People also ask

Duct leakage testing, or duct blaster testing, is required for new duct systems installed outside the thermal envelope of a home.